Description
TECHNICAL DATA | ||||
Part No. | FAE-P0621 | FAE-P0621-3 | FAE-P0621-4 | |
Model No. | AH-0621-2 | AH-0621-3 | AH-0621-4 | |
Alarm Contact | N/A | N/A | 0.8A @ 30V DC
0.4A @ 125V AC |
|
Voltage Range | 12 ~ 30V DC | |||
Alarm Current @ 24 V DC 470Ω | 50µA | 59mA | 45mA | |
Standby Current @ 24 V DC 470Ω | 140µA | 25 – 75 mA | ||
Sensitivity Setting | Comply to UL 268 | |||
Ambient Temperature | 0°C ~ +37.8°C | |||
Material | Fire-proof plastic | |||
Dimensions | 102mm (Dia.) x 48mm(H) | |||
Weight | 130g | 130g | 145g | |
Color | White | |||
ORDER INFORMATION | ||||
AH-0621-2 | 2-wire | |||
AH-0621-3 | 3-wire with remote indicator input | |||
AH-0621-4 | 4-wire with relay output | |||
EFFECTIVE ALERT AREA | ||||
Building Height | Under 4m | 4m to 20m | ||
Area Covered | 150m2 | 75m2 |