Carbon Dioxide Fire Extinguishing System
CO2 fire suppression systems are mainly used in enclosed areas that are normally not occupied by people, such as electrical, battery and generator rooms. The fire detection system is designed to activate the system when the ambient temperature and/or smoke level exceeds a predetermined limit within an enclosed area. Our CO2 fire suppression systems are rated to protect enclosed areas against Class B and E fires.
45kg Seamless Cylinder with Carbon Dioxide Gas
CO2 cylinder can be connected to a manifold via a non-return valve to enable individual containers to be removed from the system without interruption to the general protection. In general, the cylinders are grouped in rows in any combination.
Auto Gas Releasing Control Panel
A device that is designed to automatically activate the fire suppression system release sequence when fire is detected.
Standard Features
- Power Source Indicators
- Power Failure Indicators
- Zone Fire, Fault and Isolate Indicators
- Bell Isolate Switch and Indicator
- Gas Isolate Switch and Indicator
- Fault Buzzer Mute Switch
- Master Reset Switch
- Test Lamp Switch
- Test Battery Switch
- Earth Fault Supervisory
- Built-in Delay Discharge Timer (Programmable)
New Features
- GAS Abort Function (Optional)
- Digital Voltmeter and Ammeter
- Intelligent Battery Charger
- Digital Countdown Timer
- Common Fault Contact
- Low Pressure Indicator
Connecting Hose
TECHNICAL DATA Part No. HH-CH-13 Size 6mm (1/4”) Length 330mm (13”) Type High Pressure Hose Material Steel Braided Rubber Hose Test Pressure 540 bar …
Cylinder Valve
TECHNICAL DATA Part No. 45KG-NV Material Forged Brass CuZn 3963 Type Mode UP-05 Working Pressure 150bar Type Manual/Pneumatic Weight of Valve 700g Standard DIN …
Discharge Hose
TECHNICAL DATA Part No. HH-DH-17 Size 13mm (1/2”) Length 432mm (17”) Type High Pressure Hose Material Steel Braided Rubber Hose Test Pressure 385 bar …
Discharge Nozzle
Discharge nozzles are made of aluminium with female pipe threads. These nozzles are available in two configurations, 180° sidewall and 360° central discharge patterns.
Emergency Key Box
[et_pb_section fb_built=”1″ _builder_version=”3.22″ background_color=”rgba(255, 255, 255, 0)” custom_padding=”0px||||false|false” global_colors_info=”{}”][et_pb_row _builder_version=”3.25″ background_size=”initial” background_position=”top_left” background_repeat=”repeat” width=”100%” custom_padding=”0px||0px||false|false” global_colors_info=”{}”][et_pb_column type=”4_4″ _builder_version=”3.25″ custom_padding=”|||” global_colors_info=”{}” custom_padding__hover=”|||”][et_pb_wc_breadcrumb _builder_version=”3.0.47″ global_colors_info=”{}”][/et_pb_wc_breadcrumb][et_pb_wc_cart_notice _builder_version=”3.0.47″ …
Manual Pull Box
A device that is designed to activate the fire extinguishing system manually.
Pyrocharge with Fitting
TECHNICAL DATA Part No. 45KG-PC Material Stainless Steel Body Finishing Natural Voltage 24V
Solenoid 24V DC Pilot Cylinder
The pilot cylinder provides nitrogen gas at the pressure of 550 psi. The solenoid valve opens upon the supply of 24VDC, allowing gas to flow from the cylinder onto the manual / pneumatic actuator fitted to the pilot valve. The pilot valve then opens, releasing gas onto the C02 pneumatic valve. The pilot cylinder may also be operated manually, either locally at the pilot cylinder or remotely by pull box.
Solenoid 24V DC Tripping Device
A device that is designed to release the fire curtain when system is activated.